Data-centre AI · NVIDIA Vera Rubin
NVIDIA Vera Rubin: the systems, the specs and what your site needs
Vera Rubin is NVIDIA's platform for agentic AI: seven new chips built into five kinds of rack that work as one AI supercomputer. This page explains each system NVIDIA offers, the key figures from NVIDIA's datasheet, the power and cooling a site needs, and how to ask us for a quote.
- 72 + 36Rubin GPUs and Vera CPUs in one NVL72 rack
- 20.7 TBHBM4 GPU memory per NVL72 rack
- 187–227 kWPower per NVL72 rack (MaxQ to MaxP)
- 45°CWarm-water inlet, 100% liquid cooled
What Vera Rubin is
NVIDIA describes Vera Rubin as a POD: five purpose-built rack-scale systems that run together as one AI supercomputer. They are the Vera Rubin NVL72 compute rack, the Vera CPU rack, the Groq 3 LPX inference rack, the Vera BlueField-4 STX storage rack and the Spectrum-6 SPX networking rack. All of them use NVIDIA's third-generation MGX rack, so they share the same power, cooling and mechanical design.
The chips inside are the Rubin GPU, the Vera CPU, the NVLink 6 switch, the ConnectX-9 SuperNIC, the BlueField-4 DPU, the Spectrum-6 Ethernet switch and the Groq 3 LPU. A full POD, as NVIDIA's technical blog describes it, has 40 racks and 1,152 Rubin GPUs.
NVIDIA says Vera Rubin is in full production, with system makers including Dell Technologies, HPE, Lenovo and Supermicro building it. NVIDIA projects that a Vera Rubin NVL72 rack delivers AI inference at one-tenth the cost per million tokens of a GB200 NVL72 rack, and trains large mixture-of-experts models with one-quarter of the GPUs. These are vendor projections, not independent benchmarks.
The systems NVIDIA offers
Vera Rubin NVL72
The core compute rack: 72 Rubin GPUs and 36 Vera CPUs joined by sixth-generation NVLink into one domain. It has 20.7 TB of HBM4, up to 54 TB of LPDDR5X and up to 75 TB of fast-access memory. The datasheet gives 3,600 petaFLOPS of NVFP4 inference (sparse) and 216 TB/s of NVLink bandwidth. It is built from 18 compute trays and 9 NVLink switch trays.
DGX Vera Rubin NVL72
NVIDIA's own turnkey version of the NVL72 rack, for DGX SuperPOD deployments. NVIDIA lists 144 ConnectX-9 ports at 800 Gb/s, 18 dual-port BlueField-4 DPUs, NVIDIA Mission Control, NVIDIA AI Enterprise and DGX OS, with three years of enterprise support. NVIDIA marks these specifications as preliminary.
DGX Rubin NVL8
An 8-GPU DGX system with two Intel Xeon 6776P processors. NVIDIA lists 2 TB of GPU memory, 400 petaFLOPS of NVFP4 inference (sparse), 24 TB/s of NVLink Switch bandwidth and about 24 kW of system power.
HGX Rubin NVL8 and HGX Vera Rubin NVL8
The 8-GPU baseboard that server makers build into their own systems. HGX Rubin NVL8 pairs eight Rubin GPUs with an x86 CPU board; HGX Vera Rubin NVL8 pairs them with one Vera CPU (88 cores, up to 1.5 TB of LPDDR5X). The datasheet gives 400 petaFLOPS of NVFP4 inference, 2 TB of HBM4 and a 45°C inlet temperature. NVIDIA says it delivers up to 10x the token throughput of HGX B200.
Vera Rubin NVL4
Four Rubin GPUs and two Vera CPUs for liquid-cooled MGX servers, aimed at science and AI-for-science. It has up to 4.1 TB of fast-access memory. NVIDIA projects up to 4x the performance of Grace Hopper for scientific simulation, 6x for AI-for-science training and 8x for inference.
Vera CPU rack
Up to 256 Vera CPUs in a dense, liquid-cooled rack, for agent sandboxes, reinforcement learning, tool calls and data processing. NVIDIA says one rack can run more than 22,500 sandbox environments at once. Vera is also sold in standard single- and dual-socket servers.
Groq 3 LPX
An inference rack with 256 Groq 3 LPUs, each with 500 MB of on-chip SRAM. The rack has 128 GB of SRAM and 12 TB of DDR5. It works alongside Vera Rubin NVL72 for very fast, low-latency token generation. NVIDIA projects up to 35x higher throughput per megawatt for trillion-parameter models when the two are paired.
Vera BlueField-4 STX
The storage rack. BlueField-4 combines a Vera CPU and a ConnectX-9 SuperNIC. STX runs NVIDIA's CMX context memory storage, which holds the KV cache of long conversations and agent sessions so GPUs don't have to recompute it. NVIDIA says this gives up to 5x more tokens per second than traditional storage.
Spectrum-6 SPX
The networking rack that connects the POD, with Spectrum-X Ethernet or Quantum-X800 InfiniBand switches. The Spectrum-6 switch has 102.4 Tb/s of capacity and 200 Gb/s co-packaged optics in place of pluggable transceivers.
মূল স্পেসিফিকেশন
From the technical specification table in NVIDIA's Vera Rubin datasheet. A Vera Rubin Superchip is one Vera CPU with two Rubin GPUs; an NVL72 rack holds 36 of them.
| Vera Rubin NVL72 | Vera Rubin Superchip | Vera Rubin NVL4 | |
|---|---|---|---|
| কনফিগারেশন | 72 GPUs, 36 CPUs | 2 GPUs, 1 CPU | 4 GPUs, 2 CPUs |
| NVFP4 inference (sparse) | 3,600 PFLOPS | 100 PFLOPS | 200 PFLOPS |
| NVFP4 training (dense) | 2,520 PFLOPS | 70 PFLOPS | 140 PFLOPS |
| FP8/FP6 training (dense) | 1,260 PFLOPS | 35 PFLOPS | 70 PFLOPS |
| FP16/BF16 (dense) | 288 PFLOPS | 8 PFLOPS | 16 PFLOPS |
| FP64 | 2,400 TFLOPS | 67 TFLOPS | 134 TFLOPS |
| GPU মেমরি | 20.7 TB HBM4 | 576 GB HBM4 | 1.1 TB HBM4 |
| GPU memory bandwidth | 1,400 TB/s | 38.5 TB/s | 77 TB/s |
| NVLink ব্যান্ডউইথ | 216 TB/s | 6 TB/s | 12 TB/s |
| NVLink-C2C bandwidth | 65 TB/s | 1.8 TB/s | 3.6 TB/s |
| CPU cores | 3,168 Olympus cores | 88 Olympus cores | 176 Olympus cores |
| CPU মেমরি | Up to 54 TB LPDDR5X | Up to 1.5 TB LPDDR5X | Up to 3 TB LPDDR5X |
| Scale-out networking | 32.4 TB/s | 0.9 TB/s | 1 TB/s |
| Rack power | MaxP 227 kW, MaxQ 187 kW, MaxLPS 156 kW | – | – |
Source: NVIDIA Vera Rubin datasheet. NVIDIA's own product pages show some newer preliminary figures (for example up to 1,580 TB/s of GPU memory bandwidth for DGX Vera Rubin NVL72). All values are subject to change.
Power and cooling
The datasheet gives three power levels for a Vera Rubin NVL72 rack. MaxP is 227 kW, the most the rack can draw. MaxQ is 187 kW, a lower setting that NVIDIA says lets a site fit up to 30% more GPUs into the same power budget. MaxLPS is 156 kW: part of NVIDIA's DSX platform, it uses dynamic GPU power allocation, software tuning and warm-water cooling to get the most work from a fixed power budget.
The racks are 100% liquid cooled and designed for a 45°C warm-water inlet. NVIDIA says this lets many sites use dry coolers and outside air instead of chillers, which lowers PUE. Rack-level capacitors smooth the sharp power swings of AI training, and NVIDIA says this cuts peak current demand by up to 25%.
What it means for data-centre planning
Plan power per rack, not per server. One Vera Rubin NVL72 rack needs about 187–227 kW, roughly ten times the 20 kW or so that many data centres allow per rack today. Even an 8-GPU DGX Rubin NVL8 system needs about 24 kW.
Plan for liquid cooling from day one: coolant distribution units, a warm-water loop and leak containment. NVIDIA says sites already built for liquid cooling can take Vera Rubin without redesigning their cooling. NVIDIA's blog also puts an NVL72 rack at roughly 4,000 lb (about 1.8 tonnes), so check floor loading as well.
Plan the whole POD, not just the GPUs. Agentic AI needs CPU racks for sandboxes, fast storage for the KV cache and a high-speed network, and NVIDIA designed these to share the same rack, power and cooling envelope.
Plan time for compliance. High-end NVIDIA GPUs are export-controlled and allocated to a named end user and site, so suppliers need those details before they can confirm stock, price or delivery.
Availability and how to buy
Vera Rubin systems are allocated by NVIDIA and the server makers. We don't hold stock on the shelf: prices, allocation and lead times are available on request, and we confirm them with our suppliers on a written quote.
Search our shop for Vera Rubin to request a quote, or talk to our AI sales engineer, who will ask the four short compliance stages for you. Read the technical note for the full architecture.
Request a quote in our shop →NVIDIA compliance: what we need from you →Read the technical note →NVIDIA's Vera Rubin page →Vera Rubin datasheet (PDF) →
Sources
Figures are NVIDIA's published specifications and projections, many marked preliminary and subject to change; they are not our own measurements. We don't quote stock, prices or delivery dates on this page: ask us and we confirm them with our suppliers.